Home About Us Products Certificates Distributors NewsNewsArticles Contact

Home / Technical Guides / Class 150 vs Class 300

Technical Data

Class 150 vs Class 300 Malleable Iron Fittings: Reading Pressure Ratings

PT Tri Sinar Purnama · 21 November 2026 · 4 min read

Baca dalam Bahasa Indonesia →

Class 150 and Class 300 are pressure classes for malleable iron fittings in the American standard family (ASME B16.3). The class sets the maximum working pressure at a given temperature — the higher the temperature, the lower the permitted pressure.

Quick Answer

Key figures from TSP’s catalogue (American family):

  • Class 150: max 20.7 bar at −29 to 66 °C, falling to 10.5 bar at 175 °C.
  • Class 300, ¼″–1″: max 137.9 bar at −29 to 66 °C.
  • For Class 300 the rating also depends on size: larger sizes have lower ratings.
  • European family (EN 10242): 25 bar at −20 to 120 °C.

Class 150 rating table

Service temperature (°C)Max working pressure (bar)
−29 to 6620.7
10017.5
12515.2
15012.8
17510.5

American family, Class 150. Source: TSP Technical Data page (transcribed from catalogue).

Class 300 rating table

Service temperature (°C)¼″–1″ (bar)1¼″–2″ (bar)2½″–3″ (bar)
−29 to 66137.9103.469.0
100119.690.561.5
15093.171.850.7
20066.653.139.8
25040.134.528.9
28820.720.720.7

American family, Class 300 (selected rows). The full table in 25 °C steps is on TSP’s Technical Data page.

Full data, including 125, 175, 225 and 275 °C, is on Technical Data.

How to read a rating table

  1. Find your system’s maximum operating temperature.
  2. Find that temperature row (or the next higher row if there is no exact match).
  3. For Class 300, choose the column for the fitting size.
  4. Confirm the system’s working pressure does not exceed the table value, applying any safety factor in the project specification.
These are standard/family-level ratings, not per-product test results. Confirm the applicable standard and class for the specific product before specifying.

Need to confirm ratings for your system?

Send the operating temperature and pressure — TSP’s team will help check the right family and class.

Class 150/300 vs EN 10242

FamilyRating methodExample
American (ASME B16.3)Class 150 and Class 300 pressure–temperature tablesClass 150: 20.7 bar at −29 to 66 °C
European (EN 10242)Maximum permissible working pressure25 bar at −20 to 120 °C; 20 bar at 300 °C, interpolated between

Because the rating methods differ, do not compare numbers across families without checking temperature and standard.

Why the rating can be relied on

A rating only means something if production is controlled. At TSP, chemistry is checked by spectrometer four times a day, tensile tests apply a 350 N/mm² minimum with 6% elongation, and 100% of products are leak-tested at a minimum of 7 bar before packing (Quality Control).

Conclusion

Class 150 and Class 300 are ASME B16.3 pressure classes; ratings fall as temperature rises and, for Class 300, also vary with size. Use the pressure–temperature table for the right standard family and confirm the class for the specific product.

Need Class 150 or Class 300 fittings?

Discuss the right standard family and class for your system with TSP.

Frequently Asked Questions

What is the difference between Class 150 and Class 300 fittings?

Both are ASME B16.3 pressure classes. Class 300 has much higher ratings; at −29 to 66 °C, Class 150 is rated 20.7 bar while Class 300 ¼″–1″ is rated 137.9 bar.

Why does the pressure rating drop with temperature?

Material strength decreases at higher temperature, so the allowable working pressure is reduced according to the standard’s table.

Is the Class 300 rating the same for all sizes?

No. TSP’s catalogue data gives separate columns for ¼″–1″, 1¼″–2″ and 2½″–3″, with lower ratings for larger sizes.

What is the EN 10242 rating?

Per TSP’s catalogue data for the European family: 25 bar at −20 to 120 °C and 20 bar at 300 °C, interpolated between.

Where can I find TSP’s full rating tables?

On the Technical Data page at trisip.com, transcribed from TSP’s product catalogues.

Related Guides

Data sources: pressure–temperature tables on trisip.com Technical Data (TSP catalogues); Quality Control page.